eGospodarka.pl
eGospodarka.pl poleca

eGospodarka.plNieruchomościGrupypl.misc.budowanieile kW na budoweRe: ile kW na budowe
  • Path: news-archive.icm.edu.pl!news.gazeta.pl!newsfeed.pionier.net.pl!news.nask.pl!new
    s.nask.org.pl!news.onet.pl!not-for-mail
    From: "Druid29" <d...@p...onet.pl>
    Newsgroups: pl.misc.budowanie
    Subject: Re: ile kW na budowe
    Date: Mon, 30 Mar 2009 13:13:45 +0200
    Organization: http://onet.pl
    Lines: 19
    Message-ID: <gqq9hs$4q7$1@news.onet.pl>
    References: <gqq154$6m5$1@inews.gazeta.pl>
    <3...@e...googlegroups.com>
    NNTP-Posting-Host: amon.pke.pl
    X-Trace: news.onet.pl 1238411645 4935 195.245.224.251 (30 Mar 2009 11:14:05 GMT)
    X-Complaints-To: n...@o...pl
    NNTP-Posting-Date: Mon, 30 Mar 2009 11:14:05 +0000 (UTC)
    X-Priority: 3
    X-MSMail-Priority: Normal
    X-Newsreader: Microsoft Outlook Express 6.00.2900.5512
    X-RFC2646: Format=Flowed; Original
    X-MimeOLE: Produced By Microsoft MimeOLE V6.00.2900.5579
    Xref: news-archive.icm.edu.pl pl.misc.budowanie:354839
    [ ukryj nagłówki ]


    Użytkownik <w...@i...pl> napisał w wiadomości
    news:39efa88c-a5a2-4e9d-8b4b-41fb3c31d427@e5g2000vbe
    .googlegroups.com...
    Na agregat tynkarski potrzebujesz bezpiecznik 20A. Czyli moc ok. 13kW
    chyba.

    Jest to najmocniejsze narzędzie jakie będzie Ci potrzebne na budowie.
    Miksokrety mają z reguły własne silniki spalinowe. Betoniarka używana
    sporadycznie, zresztą na 20A spokojnie będzie działać.

    ==================================================
    Trzeba dodać że do agregatu tynkarskiego potrzebny jest bezpiecznik zwłoczny
    czyli C20. Zabezpieczenie przedlicznikowe powinno być przynajmniej o stopień
    mocniejsze, czyli C25.

    Pozdrawiam,
    Druid29